CVM-NRG96

M9817250120-03-05A

31

MODBUS

©

Protocol


The CVM-NRG96 power analyzers communicate by using MODBUS© protocol,
described below:

In the MODBUS protocol the RTU (Remote terminal Unit) mode is used; each 8-bit
byte in a message contains two 4-bits hexadecimal characters.

The format for each byte in RTU mode

Code

8 bit binary, hexadecimal 0-9, A-F

2 hexadecimal characters contained in each 8-bit
field in the message.

Bits per byte

8 data bits

Field Check-Error

CRC Type (Cyclical Redundancy Check)



Modbus functions used

Function 01

Reading the status of the relays


Function 03 and 04

Reading n Words (16 bits-2 bytes). Function used for
reading the electrical parameters that the CVM-NRG96 is
measuring. All electrical parameters are long with 32 bits,
because of this two Words are required to request each
parameter.

(4 bytes - XX XX XX XX)


Function 05

Writing a relay.