CVM-NRG96

M9817250120-03-05A

34

Example of a MODBUS© question


QUESTION
0A 04 00 00 00 0A 71 76

0A

Peripheral number, 10 in decimal

04

Reading function

00 00

Record at which the reading is to start

00 0A

Number of recording to be read: 10 in decimal

71 76

CRC Character


RESPONSE
0A 04 14 00 00 08 4D 00 00 23 28 00 00 0F A0 00 00 00 90 00 00 00 60 CB 2E

0A

Number of the peripheral that is responding, 10 in decimal

04

Reading function- the one used in the question

14

Number of bytes received (20).

00 00 08 4D

V1x 10 (record 00 Hex) with value in decimal 212.5 V

00 00 23 28

mA 1, in decimal 9000 mA

00 00 0F A0

W 1, in decimal 4000 W

00 00 00 90

varL 1, in decimal 144 varL

00 00 00 60

PF1 x 100, in decimal 96

CB 2E

CRC Character


*Each Modbus frame has a maximum limit of 20 variables (40 recordings).