CIRCUTOR CVM96 Series User Manual

Page 16

Advertising
background image

















----- Supply network analyzer CVM 96 ---------- ------- Page No. 15

5.- SETUP PROCEDURE

The SETUP procedure of the CVM 96 is performed by means of several

SETUP options.

For accessing the SETUP menu the keys max & min must be

simultaneously pressed once the instrument is at the main screen.

When accessing the SETUP, the message "SETUP unloc " (1) is shown for

some seconds on screen, or, otherwise, the message "SETUP loc" (2).

(1) SETUP UNLOC (SETUP unlocked ) : when the SETUP is accessed,
configuration parameters can be either visualized and modified.
(2) SETUP LOC (SETUP locked ) : when the SETUP is accessed,
configuration parameters can be visualized but cannot be modified .
Once into the SETUP, use the keyboard to select different options and enter

required variables:

- The key

validates de value and pass to the next menu.

- The key MAX permits to select among different options in a menu, or to

increase a digit when a variable is being entered.

- The key MIN permits to move the cursor along the digits.

Different options are following shown in a sequential mode:

1. Choice of visualization of phase-to-neutral or phase-to-phase voltages
2. Voltage display mode
3. Voltage transformation ratio.
4. Value of the current transformer primary : 1 a 10000 A
5. Power demand meter setting
6. Choice of default initial screen
7. Time for display shutdown
8. Deleting energy counters
9. Choice of harmonic distortion determination mode: d% or THD%
10. Setting alarms : RELAY 1 (OUT 1) & RELAY 2 (OUT 2)