background image

















----- Supply network analyzer CVM 96 ---------- ------- Page No. 38


MODBUS REGISTERS

HEXA-DECIMAL

(longs)

PARAMETER

Units

PRESENT

Value

MAXIMUM

Value

MINIMUM

Value

Frequency (L1) - Hz

Hz x 10

28-29

88-89

E8-E9

Line voltage L1-L2 - V12

V x 10

2A-2B

8A-8B

EA-EB

Line voltage L2-L3 - V23

V x 10

2C-2D

8C-8D

EC-ED

Line voltage L3-L1 - V31

V x 10

2E-2F

8E-8F

EE-EF

%THD V 1

% x 10

30-31

90-91

F0-F1

%THD V 2

% x 10

32-33

92-93

F2-F3

%THD V 3

% x 10

34-35

94-95

F4-F5

%THD I 1

% x 10

36-37

96-97

F6-F7

%THD I 2

% x 10

38-39

98-99

F8-F9

%THD I 3

% x 10

3A-3B

9A-9B

FA-FB

Active energy – kWh

Wh

3C-3D

Inductive reactive energy -
kvarh L

varLh 3E-3F

Capacitive reactive energy -
kvarh C

varCh 40-41

Three phase apparent
power

kVA III

42-43

A2-A3

102-103

Power demand

Pd

44-45

A4-A5

Corriente trifásica – AIII

mA

46-47

A6-A7

106-107

Neutral current

mA

48-49

A8-A9

108-109

Power demand (L1)*

Md (Pd)

44-45

A4-A5

Power demand (L2)*

Md (Pd)

52-53

B2-B3

Power demand (L3)*

Md (Pd)

54-55

B4-B5


* This parameters are only enabled if the maximum demand by line current has been
previously programmed