CIRCUTOR CVM96 Series User Manual

Page 9

Advertising
background image

















----- Supply network analyzer CVM 96 ---------- ------- Page No. 8

3.3.- CVM 96 (RS-232) Connection terninal (see lable on the rear part)













No.

10

11
12
13
14
15
16
17
18

1
2
3
4
5
6
7
8
9


1
2

Terminal description

Upper connection terminal

Relay RL1 output
Relay RL2 output
Relay common

Current AL3 - S2 input
Current AL3 - S1 input
Current AL2 - S2 input
Current AL2 - S1 input
Current AL1 - S2 input
Current AL1 - S1 input

Lower connection terminal

*Supply voltage input: 0 V
*Supply voltage input:230 Va.c.
RS-232 (Tx )
RS-232 (Rx )

RS-232 ( GND )
Neutral measurement
VL3 measurement
VL2 measurement
VL1 measurement

*Lower connection terminal
(SDC Model)

Supply voltage (+) d.c.
Supply voltage (-) d.c.

NOTE: Terminals 13, 15, 17 are internally connected to the 6 terminal (Neutral)
... / 5 A current inputs are isolated for the ITF model.

S2 S1 S2 S1 S2 S1

10 11 12 13 14 15 16 17 18

L3

S2

S1

RELAY ALARM

RL2 COM

RL1

S2

S1

L2

S2

S1

L1

23

0 V

0

N VL3 VL2 VL1

RS-232

(Tx) (Rx) GND

Advertising