----- Supply network analyzer CVM 96 ---------- ------- Page No. 19

NOTES:

- The secondary of the current transformers is not programmable. It is

automatically set at 5 A (... / 5 A ac)

- The primary current value to be set is also limited by the following condition:

The maximum allowable primary current value which can be set is defined by
the fact that the multiplication of the primary voltage value by this primary
current value cannot exceed 20,000,000.

5.5.- Setting power demand utility screens.

Push the key "

" and the following screens will appear by display:

1.- PARAMETER TO CONTROL ("Pd Code xx")

None

00

Three phase active power

kW III

16

Three phase apparent power kVA III

34

Average three-phase current

AIII

36

Current per phase

A1 – A2 – A3 A-PH

Value of power integrated during the programmed demand period.

2.- DEMAND PERIOD ( 1 to 60 min.) ("Pd Per xx")
3.- CLEAR MAXIMUM VALUE IN MEMORY

("CLr Pd xx") no or YES

Programming mode:

- "max" key: allows choosing the different available options.
- "min" key: allows the validation of the blinking digit and go forward to the next

digit (only for the "Pd Per xx" option).

- To pass to the next option press "

".

If you don't want to modify anything, just press the "

" key three times without

modifying any value.