----- Supply network analyzer CVM 96 ---------- ------- Page No. 42

11.- APPENDIX A: Second SETUP of the CVM 96

A second SETUP menu is accessible in order to perform the configuration of

the CVM 96 with other features different from factory-supplied ones.


To access this menu proceed as follows:

- Being the CVM 96 powered off, simultaneously press "

", "max" and

"min" keys.

- Holding these keys pressed, powered the CVM 96 on.

Following messages will be then shown on display:


a.- COMMUNICATION PROTOCOL: MODBUS

SET

PROT

Protocol:

BUS

MODBUS

(c)

(BUS) protocol

(*) See related section in this manual

- "

" key: to validate the choice and pass to the next SETUP screen:


b.- SETTING COMMUNICATION PARAMETERS

SET

Cdef

Default configuration

NO

"max" key to switch from NO / YES

- If YES is chosen: the configuration is 001 / 9600 / 8 bits / N / 1 bit