4�8�2� Selecting the maximum demand variable

SET PD V

P (W)

In this step the variable for calculation the maxi-

mum demand is programmed.
Press the

button to select between the pos-

sible options:

W: Active power.

VA: Apparent power.

mA: Current III

Press the

key to access the next programming step.

4�8�3� Period of maximum demand integration

Set PD 

015

In this step the maximum demand integration

period is programmed.
Press the

button to increase the digit that is

currently flashing.

When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the remaining values.

Maximum value: 60 minutes.

Minimum value: 1 minute.

Press the

key to access the next programming step.

4�8�4� Contracted power

Set  (W/v/m)

_05000

In this step the contracted power for the installa-

tion is programmed.
Press the

button to increase the digit that is

currently flashing.

When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the remaining values.

Maximum value: 500,000 (W /VA / mA)

Minimum value: 0 (W /VA / mA)

Press key

to access the next programming step.

4�8�5� Deleting the maximum demand maximum value�

Clea PD mAX

NO

In this step you select whether or not to delete

the maximum demand maximum value.
Press the

button to select between the two

possible options: No or Yes.

20

MDC-4

Instruction Manual