5�- TECHNICAL FEATURES

AC power supply

Rated voltage

110 ...240 V ~

Frequency

50 / 60Hz

Consumption

4...6 VA

Installation category

CAT III 300 V

Voltage measurement circuit

Rated voltage (Un)

300 V P-N, 520 V P-P

Voltage measurement margin

5 ... 120% Un

Frequency measurement margin

45 ... 65Hz

Input impedance

400kΩ

Minimum measurement voltage (Vstart)

15 V

Installation category

CAT III 300 V

Current measurement circuit

Nominal current (In)

... / 0.250 A

Current measurement margin

5 ... 100% In

Minimum measurement current (Istart)

10 mA

Installation category

CAT III 300 V

Measurement accuracy

Accuracy in voltage measurement

0.5%

Accuracy in current measurement

0.5%

Accuracy in power measurement

1%

Relay outputs

Quantity

4

Maximum voltage, open contacts

250 ~

Maximum current

6 A

Maximum switching power

750 W

Electrical working life (250 VAC / 5A)

60x10

3

cycles

Mechanical working life

10x10

6

cycles

User interface

Display

Alphanumeric LCD screen,

2 lines each containing 20 characters

Keys

4 keys

LED

5 LEDs

Environmental features

Operating temperature

0ºC ... +50ºC

Storage temperature

-10ºC ... +60ºC

Relative humidity (non-condensing)

5 ... 95%

Maximum altitude

2,000 m

Protection degree

IP20

Mechanical features

Dimensions

Figure 8

Weight

250 gr

Enclosure

UL94-V0 self-extinguishing plastic

25