4

INSTALLATION AND START UP

This section contains information instructions and warnings that the user must follow by its own security
and to ensure safe operation of the device.

WARNING! Computer MAX

regulators are usually connected to equipment containing

capacitors, which remain charged after removing supply voltage. To avoid risk of electric
shock, you must wait at least 5 minutes between the disconnection of the equipment and
handling of the internal components thereof.

Any handling or use of equipment in different way or conditions to that specified by
the manufacturer, may compromise the user safety.

In case that some damage or deterioration signs are detected in the device or a wrong operation is
observed, disconnect the supply voltage and contact CIRCUTOR authorized technical service.

To safely use the

Computer

MAX

6 and

Computer

MAX

12 it is important that people installing it or

handling it follow the usual safety precautions stated in the LV or MV Electrical Code Rules of each
Country as well as the different warnings stated in this instruction manual.

4.1

Technical Characteristics

The main technical characteristics of every particular computer

MAX

6 and computer

MAX

12 device

are printed in the rear label (see fig. 1.2) and are also summarized in the following table.

Supply and measuring circuit
voltage (Terminals C-D)

480, 400, 230 or 110 V

ac

; +15% -10% (depending on model);

45…65 Hz. Connect preferably to phases L2-L3.

Supply Cables

Cross Section 1,5 mm

2

Supply circuit protection

By means of a 0,5 to 2 A fuse (gl type)

Current measurement circuit.
(Terminals A-B)

External Current Transformer (CT). Current ratio I

n

/5. To be placed

preferably in phase L1.

Cables for the current
measurement circuit (CT
secondary side)

Minimum cross section : 2,5 mm

2

. If cable length between regulator

and CT must exceed 25 m, increase the cross section by 1mm

2

every

10 m or use a CT with a higher primary rated current.

Current margin

0,05 to 5 A (MAXimum overload +20%)

Measurements precision

Voltage and Current: 1%; cos

 : 2%  1 digit

cos

setting margin

0,85 ind. A 0,85 cap. Default setting: 1

Power Consumption
(depending on model)

110 V: 7 VA (no load); 8,8 VA (6 relays); 10 VA (12 relays)
230 V: 7,4 VA (no load); 8,2 VA (6 relays); 9,9 VA (12 relays)
400 V: 5 VA (no load); 6,6 VA (6 relays); 8,8 VA (12 relays)
480 V: 8,7 VA (no load); 9,5 VA (6 relays); 10,7 VA (12 relays)

Screen

1 line x 3 digits x 7segments + 20 icons

Output: Relay contacts

Working voltage: 250 V

ac

, Admissible current: 4 A, AC1.

Cabling and protection of
relays output.

Minimum cables cross section: 1,5 mm

2

, Protect by means of a circuit

breaker 6 A, curve C or fuse 6 A, gl type

Alarm relay

In case that not all the relay outputs are used to drive the capacitors,
the highest number relay is by default configured as alarm relay.

Reference standards

EN 61010, EN 61000-3-2, EN 61000-3-3, EN 50081-2, EN 50082-1, EN
50082-2, EN 61000-4-2, EN 61000-4-4, EN 61000-4-8,
EN 61000-4-5, EN 61000-4-11 , UL 94

Safety and Insulation class

Installation Category III. Protection against electrical shock with
double insulation (class II ), according to EN 61010-1

Protection degree

IP 40 (device mounted in panel front)
IP 30 (device case) according to EN-60529

Environment admissible
conditions

Temperature: -20 … +60 ºC; Relative humidity: MAX. 95% (without
condensation). MAX. altitude: 2000 m

Control system