4installation and start-up – CIRCUTOR computer MAX f Series User Manual

Page 10

Advertising
background image

M066B01-03-15A

computer MAX 6f 12Vdc

- 9 -

4

INSTALLATION AND START-UP

This section contains information and warnings that the user must respect at all times to guarantee
his/her own safety and the safe operation of the unit.

WARNING! The Computer MAX 6f V12dc regulators are connected to units with capacitors
that remain charged even after the voltage has been disconnected. Wait at least 5 minutes
after the unit has been disconnection, before the internal components of the equipment are
handled, in order to avoid the risk of electric shock.

Handling or use of the unit other than that specified by the manufacturer may
compromise user safety.

The power supply must be disconnected from the unit when it shows signs of deterioration or faulty
operation. In this case, contact a qualified service representative.

The persons responsible for the installation or operation of the computer MAX 6f 12 Vdc regulator must
follow common electrical installation safety measures for LV or MV installations to guarantee a safe
operation, depending on the installation location. In addition, they must take into account all warnings
found in this instruction manual.

4.1

Technical features

The main features of the unit are marked on the label on the rear (see Fig. 1.2) and they are also
summarised in following the table.

Power supply and measured
voltage (Terminals C-D)

400 +15% -10%; 45-65 Hz, (see label)
It is best to connect to phases L2-L3.

Power supply cables

1.5 mm

2

cross-section

Power circuit protection

With a gl type 0.5 to 2A fuse

Current measurement circuit.
(Terminals A-B)

External current transformer (CT), In /5 ratio. It is best to connect to
phase L1.

Current measurement circuit
cables

Minimum 2.5 mm

2

cable cross-section. For distances greater than 25

m between the regulator and CT, it is recommended to increase the
cross-section to 1 mm

2

for every 10 m, or use a CT with a higher

primary In

Current measurement margin

0.05 to 5 A (maximum overload +20%)

Measurement accuracy

Voltage and current: 1%; cos

ϕ

: 2 %

±

1 digit

Cos

ϕϕϕϕ

setting range

0.85 ind. A 0.85 cap, Default setting: 1

Maximum consumption

400 V: 6.5 VA

Screen

1 line x 3 digits x 7 segments + 20 icons

Output

Static MOS. 12±2 Vdc , Max 20 mA

Reference standards

EN 61010, EN 61000-3-2, EN 61000-3-3, EN 61000-4-2,
EN 61000-4-4, EN 61000-4-8, EN 61000-4-5, EN 61000-4-11, UL 94

Safety/Insulation

Category III installation, as per EN 61010-1
Double-insulation electric shock protection, (class II unit) as per EN
61010-1

Protection degree

IP40 (unit mounted, cabinet front panel)
IP30 (unit not mounted), according to EN-60529

Admissible environmental
conditions

Temperature: -20ºC to +60ºC; Relative humidity: max 95% (non-
condensing). Max. altitude: 2000 m

Control system

FCP (Program that minimises the number of operations)

Total (Connection/Disconnection of all required capacitors)