computer MAX 6f 12Vdc

- 18 -

7.2

Behaviour of the unit during ALARM mode

If the unit detects an error (see section 3.2) the error code will be shown on the screen and the response
of the computer will act as indicated on table 7.1

Table 7-1: Unit errors and actuations

ERROR

message

Description

Possible cause and computer response

Lower current
measure at the
threshold
(0.05A on
the secondary CT)

Possible causes: Low load or CT not connected.

The unit shows the RUN LED and the screen with all
the zeros flashing, and does not connect any output

Overcompensation. A
disconnect request is
made and all the
outputs are
disconnected.

Possible causes: C/K incorrectly adjusted

No outputs are connected.

Undercompensation.
Connection is
requested and all the
outputs are connected.

Possible causes: C/K incorrectly adjusted

All the outputs remain connected except the alarm, if
triggered (see section 3.3)

Overcurrent. The
current measure
exceeds Inom + 20%.

Possible causes: C/K incorrectly adjusted

The alarm output disconnects, if triggered (see section
3.3). The unit normally tries to regulate, although it
could have a regulation error.

Overvoltage. The
voltage measure
exceeds Vnom +15%.

Possible causes: Bad voltage connection

The alarm output disconnects, if triggered (see section
3.3). The unit normally tries to regulate, although it
could have a regulation error.

8

MAINTENANCE

The computer MAX 6f 12Vdc regulator does not require special maintenance. Try to avoid any type of
adjustment, maintenance or repairs while the unit is open as much as possible. If this cannot be avoided,
only qualified and trained staff should carry out these operations.

Disconnect the unit from all power supplies before performing any connection modifications, relocation,
maintenance or repair operations. If any operational faults in the unit or in its protection elements are
suspected, remove the unit from service and make sure that accidental connection is not possible. The
design of the unit makes it easy to replace in the event of a fault.

9

TECHNICAL SERVICE

If you have any doubts about the operation of the unit or suspect any malfunction, contact our service
staff at CIRCUTOR, S.A.

CIRCUTOR, S.A. - After-Sales Service.