Installation location – CIRCUTOR OPTIM-EMS-C Series User Manual

Page 12

Advertising
background image

3.3.- INSTALLATION LOCATION

It is important to maintain a minimum distance around the unit to facilitate cooling.

As it is a wall-assembled cabinet, use the three 10 mm diameter holes made in the rear of the

cabinet for wall mounting, as shown in

Figure 5

, use suitable fixing elements for supporting its

weight.

460

710

542.7

110

76.7

306

160

160

200

Figure 5: Points for fixing OPTIM EMS-C capacitor banks to the wall.

In self-supporting cabinets, the back and front sides of the cabinet must be kept at least

60 cm

away from walls of other units and infrastructures to allow for ventilation.

As regards side walls, it is recommended leaving at least a

20 cm separation between adjacent

cabinets.

Note: Static units have an aluminium heatsink to cool the thyristors. Periodically clean these

heatsinks with a brush or with compressed air and ensure that they have maximum ventilation.

Make sure the unit can be accessed easily.

The environmental conditions of the location where the unit is installed must not exceed the

limits set forth in the technical features (See

“6.- TECHNICAL FEATURES”)

To ensure proper ventilation, the unit must be installed in a vertical position.

In accordance with the LVR, once the unit is installed, the installation must be protected against

direct and indirect contacts. Therefore, a circuit breaker and earth leakage protection for the

capacitor bank power supply line should be installed.

12

OPTIM EMS-C series

Instruction Manual

Advertising