CIRCUTOR OPTIM-EMS-C Series User Manual

Page 16

Advertising
background image

Figure 9: Current transformer (CT) connection terminals.

Once the cables are installed, disconnect the jumper connecting the S1 and S2 terminals of the

capacitor bank (

Figure 10

)

Figure 10: Jumper for short-circuiting the secondary winding of the current transformer (CT).

Any time you wish to change or disconnect a current transformer that is already

installed, it is important to install the jumper connecting S1 and S2.

16

OPTIM EMS-C series

Instruction Manual

Advertising