Basic maintenance protocol, Maintenance, Safety regulations – CIRCUTOR OPTIM-EMS-C Series User Manual

Page 20: Maintenance with the capacitor bank disconnected

Advertising
background image

5.- MAINTENANCE

5.1.- SAFETY REGULATIONS

Take the safety regulations listed in section of this manual into account before

operating the units

3.1.- PRELIMINARY RECOMMENDATIONS

The National Electric Code of the country where the capacitor bank is installed or

operated should be strictly followed.


5.2.- MAINTENANCE WITH THE CAPACITOR BANK DISCONNECTED

5.2.1. BASIC MAINTENANCE PROTOCOL

Monthly:

Visually inspect the capacitors.

Check the protection circuit breakers.

Control the ambient temperature (average of 30 ºC In accordance with IEC 60831 ).

 Control the service voltage (especially during moments of low load, it must not exceed

the nominal +10%).

Bi-annually:

Keep the capacitor and reactor terminals clean.

 Check that the thyristors are not short-circuited.

To do so, check that if you cut the power supply of the regulator there is no current in any

of the capacitor phases.
 Check that the capacitor current is not lower than 75% nor greater than 120% of the

nominal value by phase and that there is no phase unbalance greater than 15%.

Annually:

Check the capacity of the capacitors at the different steps.

An indirect verification can be performed by checking that the consumption matches the

value indicated in

Table 5

, with a maximum deviation of ± 10%.

Check the tightening torque of all terminal connections on the different power ele-

ments.

Inspect the circuit breakers.

-

Power Circuit: Check the continuity and temperature of the circuit breakers.

-

Control Circuit: Check the continuity and temperature of the two-pole circuit breaker.

20

OPTIM EMS-C series

Instruction Manual

Advertising