7.11. DIGITAL I/O

Digital I/O provide digital input as well as digital output. Each Digital I/O port can be used either as input or as
output.

Digital I/Os are applicable as follows

DIGITAL I/O 1 - 12 on ipCUE-sigma

and not applicable for ipCUE-alpha, ipCUE-beta, ipCUE-gamma, ipCUE-delta, ipCUE-epsilon.

Pull-up resistor 680 ohms is connected to +5 VDC. Digital input is rated 0 – 24 VDC, threshold is 2 V. Voltage
on I/O with open output transistor is approx. 4.3 VDC, because protection diode is connected in series (0.7 V
drop-down). Voltage on I/O for output switch on is approx. 0.6 V. Max. 24 VDC / 80 mA can be switched by
output transistor.

IO schematic diagram

Connector pin out

Note: Digital I/O is galvanically isolated from other ports.

User Manual ipCUE Controllers

www.cuesystem.com

Page 26 of 52

DIGITAL I/O on ipCUE controller

INPUT 1 – 8

value CLOSE (< 2 V) / OPEN (> 2 V)

OUTPUT 1 – 8
value CLOSE / OPEN

680 Ohm

+5 VDC

Input / Output

Common

10 kOhm

1

C

2 3 4 5 6 7 8 9 10 11 12

Pin

C

1 - 12

DIGITAL I/O

13-pin 3.5 mm

Description

Common

Input / Output Signal 1 - 12