Installation procedure, Connections gas connection, Testing lp gas safety shut off – Dometic DM2862 User Manual

Page 9: Drain water hose, Warning

Advertising
background image

- 9 -

Hole for drain

water hose

Hose

Boiler

casing

NDR1292

coNNectioNs
gas connection

Hook up to the gas supply line is accomplished at the manual

gas valve, which is furnished with a 3/8” SAE (UNF 5/8” -18)

male flare connection. All completed connections should be

examined for leaks using a solution of liquid detergent and

water.

The gas supply system must incorporate a pressure regulator

to maintain a supply pressure of not more than 11 inches water

column. When testing the gas supply system at test pressures:

> 1/2 psi

- the refrigerator and its individual shutoff valve

must be disconnected from the gas supply piping system.
≤ 1/2 psi

- the appliance must be isolated from the gas

supply piping system by closing its individual manual shut-

off valve.

If detailed instructions on the installation and connection to

the gas supply are required, please contact your dealer or

distributor.

testing lP gas safety shut off

The gas safety shut off must be tested after the refrigerator is

connected to LP gas supply.

RM2354, RM2454, RM2554, DM2662, DM2663,

DM2862, DM3862, NDM1062 & NDR1292

To test the gas safety shut off, follow these steps:

Start the refrigerator. Switch to GAS mode.

1.

Check that the gas flame is lit and the GAS mode

2.

indicator lamp is on.
Close the manual gas shutoff valve at the back of the

3.

refrigerator.
Wait for approx. 6 minutes. The ChECK indicator

4.

lamp should be lit and the GAS mode indicator lamp

should be off.
Remove the protection cover.

5.

Open the manual gas shutoff valve. Do not change

6.

any button positions on the control panel.
Apply a non corrosive commercial bubble solution

7.

to the burner jet orifice. No bubbles should appear at

the opening of the burner jet orifice. The presence of

bubbles indicates a defective gas safety shutoff, and

service is required.
If no bubbles are present at the burner jet orifice,

8.

rinse it with fresh water. Be careful not to damage the

burner jet orifice.

drain water hoSe

Drill a hole through flooring. To avoid damage to the hose,

the hole must be positioned so that the hose doesn’t touch the

boiler casing. Seal around the hose that goes through the drilled

hole and ensure that it does not kink when run through the

floor. Check to make sure that the supplied hose is long enough

in order for the water to drain outside of the vehicle. If not, the

installer will have to supply the extra length of hose.

Drill the hole in the

cut out opening of

the base plate

Hole for drain

water hose

Boiler

casing

Hose

RM2451, RM2454, RM2551, RM2554, DM2652, DM2662,

DM2663, DM2852, DM2862, DM3862 & NDM1062

Hole for drain

water hose

Boiler

casing

Hose

RM2351 & RM2354

installation procedure

wARNINg

eXPLOSION hAZARD. Never use an open

flame to check for gas leaks. Failure to heed this

warning could cause an explosion resulting in

death or severe personal injury.

6

!