12 Stove

Installation

(for qualified installers only)

© Travis Industries

100-01178

4081029

Chimney Termination Requirements

 Must have an approved cap (to prevent water from entering).
 Must not be located where it will become plugged by snow or other material.
 Must terminate at least 3' (914mm) above the roof and at least 2' (610mm) above any portion of the

roof within 10' (3.04M) - see Figure 7.

Figure 7

Outside Air Requirements

 Required for mobile homes & in certain localities (check with building officials).
 Must not be drawn from an enclosed space (garage, unventilated crawl space).
 Requires the optional outside air connector or pedestal.
 Air duct maximum length is 15’ (4.57M) with a minimum cross-section of 16 square inches

(10404mm) or 6’ (1.82M) with a minimum cross section of 7 square inches (4489mm).

Figure 8

Min. 3’ (914mm)

Min. 2’ (610mm)

10’ (3.04M)

Min. 3’ (914mm)

10’ (3.04M)

Min. 2’ (610mm)

Outside Air

Connector

Outside air entrance must be placed so

it does not become blocked by snow.

Pedestal or outside air boot may

be used to direct air from below

the stove. See the pedestal

instructions for complete details.

Air may be drawn from a ventilated

crawl space or use an air duct.

The pedestal has an air

opening for use with the

outside air connections.

This allows air to be

drawn from behind the

pedestal.