8 stove installation, Floor protection requirements, Stove placement requirements – Avalon Firestyles 1250 Wood Stove User Manual

Page 8: Clearances

Advertising
background image

8 Stove

Installation

(for qualified installers only)

© Travis Industries

100-01178

4081029

Floor Protection Requirements

 Stove must be placed on the Travis Industries legs or pedestal.
 Floor protection must extend to the sides, rear, and front of the stove (see “Clearances” below for

minimum floor protection).
NOTE: When installed with reduced-clearance connector, the clearance to the backwall may be less
than the floor protection requirement. In this case the floor protection must extend to the wall.

 Floor protection must be non-combustible and at least .018" thick (26 gauge).

Stove Placement Requirements

Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or
other means approved by local building or fire officials.

 Stove must be placed so that no combustibles are within, or can swing within (e.g., drapes, doors),

36" (914mm) of the front of the stove.

 If the stove is placed in a location where the ceiling height is less than 7' (2134mm), it must follow the

requirements in the section "Alcove Installation Requirements".

 Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):

Clearances

 The following clearances must be met (see Figure 3 and Figure 4)

Clearance Requirements:

Singlewall Connector

Reduced Clearance*

A

Sidewall to stove

18"

457mm

18"

457mm

B

Backwall to stove

18”

457mm

10-1/2" 267mm

C

Cornerwall to stove

10"

254mm

10"

254mm

D

Connector to sidewall

27"

686mm

26-1/2" 673mm

E

Connector to backwall

19-1/4" 489mm

11-1/4" 286mm

F

Connector to cornerwall

17-3/4” 451mm

17-1/4” 438mm

G

Side & Rear Floor Protector

6” 152mm (US)
8” 200mm (Canada)

6” 152mm (US)
8” 200mm (Canada)

H

Front Floor Protector

16” 406mm (US)
18” 450MM (Canada)

16” 406mm (US)
18” 450MM (Canada)

*Reduced clearance installations require one of the chimneys and connectors listed below:

AMERI-TEC model DCC with model HS chimney
DURAVENT model DVL with DURATEC or DURA-PLUS chimney
GSW Super Chimney Twenty-One connected directly to appliance
I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector
METALFAB model DW connector with TG chimney
OLIVER MACLEOD PROVENT model PV connector with model 3103 chimney
SECURITY model DP connector with SECURITY model ASHT or S2100 chimney
SELKIRK METALBESTOS model DS connector with model SSII chimney
Standard Masonry Chimney with any one of the above listed connectors

NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be

required.

NOTE: Mobile Home installations must use the reduced clearance connector and clearances listed above.

NOTE: Standard residential installations with reduced clearance connector may use the “Connector to Wall”

clearance determined by the connector manufacturer if approved by local code. This clearance is
established by the connector manufacturer and falls under the connector manufacturer’s listing. “Stove to
Wall” clearances must always be met.