Stove installation, For qualified installers only), Interior or exterior masonry chimney – Avalon Firestyles 1250 Wood Stove User Manual

Page 17

Advertising
background image

Stove

Installation

(for qualified installers only)

17

© Travis Industries

100-01178

4081029

Hearth Stove Direct
Connection

NOTE:

This type of installation is
not allowed in Canada.

NOTE:

Direct connections require
installation of an airtight,
non-combustible block-off
plate or damper adapter.

Figure 16

Interior or Exterior
Masonry Chimney

NOTE:

This type of installation is
not allowed in Canada.

NOTE:

This type of installation
requires a UBC approved
masonry connector or
other method approved by
the NFPA 211 standard.
See Chimney Connector
Requirements on page 10
for further details.

Figure 17

Block-off plate or

damper adapter

Remove damper

or wire it open

Airtight

Insulated

Clean-Out

Stainless steel

chimney connector

must Extend 1' past

the block-off plate or

to the flue liner

NOTE: The chimney must have a clay tile

liner. If it does not, the installation must use

a positive connection (full reline). The entire

fireplace and chimney must be clean,

undamaged, and meet all local building

codes (UBC, etc.). Damage must be

repaired prior to installation. The chimney

must be 15' (4.57M) to 33' (10.05M) tall.

Clay

Liner

Floor Protection

(See the section

"Floor Protection

Requirements" for

more details)

Combustible Mantle

Min. 18"

(457mm)

See the section

"Stove Placement

Requirements" for

minimum clearances

required.

Make sure the
clean-out seals in
place.

Clay Liner

See the section "Stove
Placement Requirements" for
minimum clearances required.

Min. 18"
(457mm)
clearance
to ceiling

This type of
installation requires
a UBC approved
masonry connector
or a factory built
(U.L. Listed) wall
thimble.

Chimney connector sections

NOTE: The chimney must have a
clay tile liner. If it does not, the
installation must use a positive
connection (full reline). The entire
fireplace and chimney must be
clean, undamaged, and meet all
local building codes (UBC, etc.).
Damage must be repaired prior to
installation. The chimney must be
15' (4.57M) to 33' (10.05M) tall.

See the section
"Floor Protection
Requirements"