Implementation table – Basler Electric BE1-11 DNP3 Protocol User Manual

Page 13

Advertising
background image

9424200773 Rev A

7

Implementation Table

Table 2 identifies which object variations, function codes, and qualifiers the BE1-11 DNP supports in both
request messages and in response messages.

For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08 will be responded
to with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded to with
qualifiers 17 or 28.

For change-event objects, qualifiers 17 and 28 are always responded.

Table 2. BE1-11 DNP Implementation Table

OBJECT

REQUEST

(BE1-11 will parse)

RESPONSE

(BE1-11 will respond

with)

Obj.

Var.

Description

Function

Codes (dec)

Qualifier Codes

(hex)

Function

Codes

(hex)

Qualifier

Codes

(hex)

1

0

Binary Inputs –
(Variation 0 is used to
request default variation)

1 (read)
22 (assign class)

00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

1

1

(default –

see note

1)

Single-Bit Binary Input

1 (read)
22 (assign class)

00,01 (start- stop) 06
(no range)
07,08 (limited qty)
17,28 (index)

81 (response)

00,01 (start-
stop)
17,28 (index)

1

2

Binary Input with Status

1 (read)
22 (assign class)

00,01 (start- stop) 06
(no range)
07,08 (limited qty)
17,28 (index)

81 (response)

00,01 (start-
stop)
17,28 (index)

2

0

Binary Input Change
(Variation 0 is used to
request default variation)

1 (read)

06 (no range)
07,08 (limited qty)

2

1

Binary Input Change
without time

1 (read)

06 (no range)
07,08 (limited qty)

81 (response)

17,28 (index)

2

2

(default –

see note

1)

Binary Input Change with
time

1 (read)

06 (no range)
07,08 (limited qty)

81 (response)

17,28 (index)

10

0

Binary Output –
(Variation 0 is used to
request default variation)

1 (read)

00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

10

2

(default)

Binary Output Status

1 (read)

00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

81

00,01 (start-
stop)
17,28 (index)

12

1

Control Relay Output
Block

3 (select)
4 (operate)
5 (direct op)
6 (dir op Noack)

00,01 (start-stop)
07,08 (limited qty)
17,28 (index)

81

echo of
request

30

0

Analog Input (Variation 0
is used to request default
variation)

1 (read)
22 (assign class)

00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

81 (response)

00,01 (start-
stop)
17,28 (index)

30

1

32-Bit Analog Input With
Flag

1 (read)
22 (assign class)

00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

81

00,01 (start-
stop)
17,28 (index)

BE1-11

Implementation Table