Point list, Binary input points – Basler Electric BE1-11 DNP3 Protocol User Manual

Page 21

Advertising
background image

9424200773 Rev A

15

Point List

Binary Input Points

Binary Input changes are scanned every quarter of a nominal cycle. Events are pending in the Slave
application buffer until the Master device sends confirmation that response with pending events was
received. Table 3 describes the default list of binary input points.

User can select Binary Input points from the default list in Table 3 and make active (mapped) list of points
as desired. Only all Binary Input points from “Binary User Map” list are included in Class 0, and generate
events. Only mapped points can be read through any “read” request. Mapping is only possible though
BESTCOMSPlus

®.

Class assignment for each active binary input point (point mapped to User Binary Map) is configurable via
DNP assign class function.

Device Event buffer for Binary events is 4 times the total number of Binary inputs in default list.

Default variations for objects 1 and 2 are programmable through BESTCOMSPlus or the front panel of the
BE1-11.

Assigned classes, changed via DNP, can be saved in non-volatile memory on user request, via Analog
Output Block, object 41 (point named “DNP Save Assigned Class and Deadband”).

The application type, listed in the Application column, is defined below:

F = Feeder Protection System

G = Generator Protection System

I = Intertie Protection System

M = Motor Protection System

T = Transformer Protection System

Table 3. Binary Input Points

Binary Input Points

Static Object Number: 1
Change Event Object Number: 2

Request Function Codes Supported: 1 (read), 22 (assign class)
Static Variation Reported When Variation 0 Requested: 1 (Binary Input Without Status), Configurable
Change Event Variation Reported When Variation 0 Requested: 2 (Binary Input Change With Time),
Configurable

Point Index

Description

Class

Application

0

60FL Target

1

FGIMT

1

24 Block

1

GIT

2

24 Pickup

1

GIT

3

24 Trip

1

GIT

4

24 Target

1

GIT

5

24 Volts Per Hz

1

GIT

6

25 Block

1

FGI

7

25 Status

1

FGI

8

25 VM1 Status

1

FGI

9

27P-1 Block

1

FGIMT

10

27P-1 Pickup

1

FGIMT

BE1-11

Point List