Basler Electric BE1-11 DNP3 Protocol User Manual

Page 14

Advertising
background image

8

9424200773 Rev A

OBJECT

REQUEST

(BE1-11 will parse)

RESPONSE

(BE1-11 will respond

with)

Obj.

Var.

Description

Function

Codes (dec)

Qualifier Codes

(hex)

Function

Codes

(hex)

Qualifier

Codes

(hex)

30

2

16-Bit Analog Input With
Flag

1 (read)
22 (assign class)

00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

81

00,01 (start-
stop)
17,28 (index)

30

3

(default –

see notes

1, 2)

32-Bit Analog Input
Without Flag

1 (read)
22 (assign class)

00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

81

00,01 (start-
stop)
17,28 (index)

30

4

16-Bit Analog Input
Without Flag

1 (read)
22 (assign class)

00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

81

00,01 (start-
stop)
17,28 (index)

30

5

Short float analog input

1 (read)
22 (assign class)

00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

81

00,01 (start-
stop)
17,28 (index)

32

0

Analog Change Event
(Variation 0 is used to
request default variation)

32

1

(default –

see notes

1, 2)

32-Bit Analog Input
without time

1 (read)

06 (no range)
07,08 (limited qty)

81

17,28 (index)

32

2

16-Bit Analog Input
without time

1 (read)

06 (no range)
07,08 (limited qty)

81

17,28
(index)

32

3

32-Bit Analog Input with
time

1 (read)

06 (no range)
07,08 (limited qty)

81

17,28
(index)

32

4

16-Bit Analog Input with
time

1 (read)

06 (no range)
07,08 (limited qty)

81

17,28
(index)

32

5

Short float analog
change event without
time

1 (read)

06 (no range)
07,08 (limited qty)

81

17,28
(index)

32

7

Short float analog
change event with time

1 (read)

06 (no range)
07,08 (limited qty)

81

17,28
(index)

34

0

(Variation 0 is used to
request default variation)

1 (read)
2 (write)

00,01 (start-
stop)
17,28 (index)

34

1

16-Bit Analog Input
Deadband

1 (read)
2 (write)

For read:
00,01,06,07,08,17,
28
For write:
00,01,07,08,17,28

81

00,01 (start-
stop)
17,28 (index)

34

2 (default)

32-Bit Analog Input
Deadband

1 (read)

For read:
00,01,06,07,08,17,
28
For write:
00,01,07,08,17,28

81

00,01 (start-
stop)
17,28 (index)

40

0

Analog Output Status –
(Variation 0 is used to
request default variation)

1

00,01 (start-stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

40

1

32-bit Analog Output
Status

1 (read)

00,01 (start-stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

81

00,01 (start-
stop)
17,28 (index)

Implementation Table