Basler Electric BE1-11 DNP3 Protocol User Manual

Page 15

Advertising
background image

9424200773 Rev A

9

OBJECT

REQUEST

(BE1-11 will parse)

RESPONSE

(BE1-11 will respond

with)

Obj.

Var.

Description

Function

Codes (dec)

Qualifier Codes

(hex)

Function

Codes

(hex)

Qualifier

Codes

(hex)

40

2 (default)

16-bit Analog Output
Status

1 (read)

00,01 (start-stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

81

00,01 (start-
stop)
17,28 (index)

40

3

Short float Analog
Output Status

1 (read)

00,01 (start-stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

81

00,01 (start-
stop)
17,28 (index)

41

1

32-bit Analog Output
Block

2 (select)
3 (operate)
4 (direct op)
6 (dir op noack)

00,01 (start-stop)
07,08 (limited qty)
17,28 (index)

81

echo of
request

41

2

16-bit Analog Output
Block

3 (select)
4 (operate)
5 (direct op)
6 (dir op noack)

00,01 (start-stop)
07,08 (limited qty)
17,28 (index)

81

echo of
request

41

3

Short Float Analog
Output Block

3 (select)
4 (operate)
5 (direct op)
6 (dir op noack)

00,01 (start-stop)
07,08 (limited qty)
17,28 (index)

81

echo of
request

50

1

Time and Date

1 (read)
2 (write)

00,01 (start-stop)
06 (no range or all)
07 (limited qty=1)
08 (limited qty)
17,28 (index)

81

00,01 (start-
stop)
17,28 (index)

60

1

Class 0 Data (Note 4)

1 (read)

06 (no range or all)

81

60

2

Class 1 Data

1 (read)
20 (enable
unsol)
21 (disable
unsol)
22 (assign class)

06 (no range or all)
07,08 (limited
quantity)

81

60

3

Class 2 Data

1 (read)
20 (enable
unsol)
21 (disable
unsol)
22 (assign class)

06 (no range or all)
07,08 (limited
quantity)

81

60

4

Class 3 Data

1 (read)
20 (enable
unsol)
21 (disable
unsol)
22 (assign class)

06 (no range or all)
07,08 (limited
quantity)

81

80

1

Internal Indications

2 (write)

00 (start-stop)
(index=7)

110

Octet String

1 (read)

00,01 (start-stop)
06 (no range)
07,08 (limited qty)
17,28 (index)

81

00,01 (start-
stop)
17,28 (index)

No Object(function code
only) (See Note 3)

13 (cold restart)

No Object(function code
only) (See Note 3)

14 (warm
restart)

No Object (function code
only)

23 (delay
measurement)

BE1-11

Implementation Table

Advertising