Bit unsigned integer, object 110 – Basler Electric BE1-11 DNP3 Protocol User Manual

Page 76

Advertising
background image

70

9424200773 Rev A

Point Index

Description

0

43-1 Mode

1

43-2 Mode

2

43-3 Mode

3

43-4 Mode

4

43-5 Mode

5

101 Mode

6

Breaker Monitor Operations

7

Breaker Monitor Duty A

8

Breaker Monitor Duty B

9

Breaker Monitor Duty C

10

Demand Meter Reset Demands

11

DNP Save Assigned Class and Deadband

12

Fault Report Selection Record

13

Contact Output 1 Override Enable

14

Contact Output 2 Override Enable

15

Contact Output 3 Override Enable

16

Contact Output 4 Override Enable

17

Contact Output 5 Override Enable

18

Contact Output A Override Enable

19

Major Alarm Reset

20

Minor Alarm Reset

21

Targets Reset

22

Relay Alarms Reset

23

Settings Group Mode

24

Settings Group Operate

25

Demand Meter CT Circuit 2 Reset Current Demands

26

Demand Meter CT Circuit 2 Reset Ground Current Demands

27

Contact Output 6 Override Enable

28

Contact Output 7 Override Enable

29

Contact Output 8 Override Enable

30-32

Reserved

33

Logic Alarms Reset

8-Bit Unsigned Integer, Object 110

Table 7 is the point list for Object 110, and lists the 8-Bit Unsigned Integer Points. Note that this object
has only variation 1 and cannot be requested with default variation 0.

Point List

BE1-11