Combination with other protective devices, Model and style number, Combination with other protective devices -2 – Basler Electric BE1-50 User Manual

Page 10: Model and style number -2

Advertising
background image

In this application, the two leads of each phase of the protected motor or generator are passed through

the window of the same associated phase current transformer so that the resulting secondary current is

zero under normal operating conditions.

Figure 1-2. Self-Balancing Differential Protection

Combination with Other Protective Devices
Because BE1-50 relays can provide complete phase and ground fault protection in one unit (and with

independent settings for phase and ground), they are often used to supervise other relay functions. In

distance protection, BE1-50 relays can be used to prevent misoperation for light loading conditions by

requiring a minimum current level before enabling the distance relay. As a fault detector, they are

particularly effective because of their sensitivity, speed, and dropout ratio.

MODEL AND STYLE NUMBER

BE1-50 electrical characteristics and operational features are defined by a combination of letters and

numbers that make up the style number. Model number BE1-50 designates the relay as a Basler Electric

Instantaneous Overcurrent Relay. The model number, together with the style number, describes the

options included in a specific device and appears on the front panel, draw-out cradle, and inside the case

assembly.
The style number identification chart for the BE1-50 relay is illustrated in Figure 1-3.

1-2

BE1-50 General Information

9171000990 Rev F