Step 2. Turn the phase pickup adjustment fully CCW. For relay styles with target indicators, operate the

manual reset switch to ensure that the targets are reset.

Step 3. Apply sensing current (near zero) and slowly increase the sensed current until the test indicator

changes state.

Result: Current indicated by the ammeter is within two percent of the low end of the sensing

range. If present, the target indicator for the tested phase (or neutral) should be

actuated.

Step 4. Turn the pickup adjustment fully CW. Reset target indicators if present.
Step 5. Apply sensing current (near zero) and slowly increase the sensed current until the test indicator

changes state.

Result: Current indicated by the ammeter is within two percent of the high end of the sensing

range. If present, the target indicator for the tested phase (or neutral) should be

actuated.

Step 6. Repeat Steps 2 through 5 for each phase and neutral as necessary for your style relay. (Neutral

sensing ranges may be different from the phase sensing range.)



5-2

BE1-50 Testing

9171000990 Rev F