SECTION 1 • GENERAL INFORMATION

PURPOSE

Instantaneous overcurrent relays provide phase and ground fault protection for distribution circuits,

generators, motors, transformers, and other major components of power systems. BE1-50 Instantaneous

Overcurrent relays have a wide range of pickup settings and input configurations to accommodate

protection requirements for power systems. BE1-50 relays are available in single or multi-phase for power

units.

APPLICATION

Some applications are illustrated in Figure 1-1.

Figure 1-1. Typical BE1-50 Applications

Ground Fault Detection
BE1-50 relays can be applied to monitor zero sequence currents that are indicative of ground faults. The

most sensitive method of ground fault protection utilizes a single current transformer through which all the

conductors are passed (Figure 1-1b). Another method uses the residual connection of the three-phase

CTs (Figure 1-1d) with the relay set higher than the normal system unbalance. The most direct method is

to place a CT in the neutral of a grounded wye connection for equipment such as power transformers or

generators (Figure 1-1c).

Phase Fault Detection
BE1-50 relays can be used in two ways to detect phase faults. The first method is to place an

instantaneous overcurrent element in each phase with the setting higher than expected load current for

any power system element (Figure 1-1a, d, e, f). The second method is called self-balancing differential

protection (Figure 1-2).

9171000990 Rev F

BE1-50 General Information