Power supply, Target indicators, Type tests – Basler Electric BE1-50 User Manual

Page 13: Physical, Power, Supply -5, Target, Indicators, Type, Tests

Advertising
background image

Power Supply
Externally powered power supply types are listed in Table 1-2.

Table 1-2. Power Supply Ratings

Type

Nominal

Input Voltage

Input Voltage Range

Burden at Nominal

O (midrange)

48 Vdc

24 to 150 Vdc

1.2 W

P (midrange)

125 Vdc

24 to 150 Vdc

1.5 W

120 Vac

90 to 132 Vac

19.3 VA

R (low range)

24 Vdc

12 to 32 Vdc ∗

1.3 W

S (midrange)

48 Vdc

24 to 150 Vdc

1.2 W

125 Vdc

24 to 150 Vdc

1.5 W

T (high range)

250 Vdc

68 to 280 Vdc

1.7 W

240 Vac

90 to 270 Vac

31.6 VA

Type R power supply initially requires 14 Vdc to begin operating. Once operating, the input voltage may

be reduced to 12 Vdc and operation will continue.

Target Indicators
Electronically latched, manually reset target indicators are optionally available to indicate closure of the

trip output contacts. Either internally operated or current operated targets may be specified. Internally

operated targets should be selected when normally closed (NC) output contacts are specified.
Current Operated Targets

Minimum Rating:

200 mA flowing through the trip circuit

Continuous Rating:

3 A

1 Second Rating:

30 A

2 Minute Rating:

7 A

Type Tests
Shock:

Withstands 15 G in each of three mutually perpendicular planes

without structural damage or performance degradation.

Vibration:

Withstands 2 G in each of three mutually perpendicular planes,

swept over the range of 10 to 500 Hz for a total of six sweeps, 15

minutes each sweep, without structural damage or degradation of

performance.

Dielectric Strength:

Tested in accordance with IEC 255-5 and IEEE C37.90. All circuits to

ground: 2,121 Vdc. Input to Output circuits: 1,500 Vac/2,121 Vdc.

Radio Frequency Interference:

Maintains proper operation when tested for interference in

accordance with IEEE C37.90.2-1987, Standard Withstand

Capability of Relay Systems to Radiated Electromagnetic

Interference from Transceivers.

Surge Withstand Capability:

Qualified to IEEE C37.90.1-1989, Standard Surge Withstand

Capability (SWC) Tests for Protective Relays and Relay Systems.

Physical
Temperature

Operating Range:

–40 to 70°C (–40 to 158°F)

Storage Range:

–65 to 100°C (–85 to 212°F)

Weight:

17.5 lb (7.76 kg)

Case Size:

S1 (Refer to Section 4 for case dimensions.)

9171000990 Rev F

BE1-50 General Information

1-5

Advertising