SECTION 3 • FUNCTIONAL DESCRIPTION

INTRODUCTION

BE1-50 Instantaneous Overcurrent relays are static devices that respond to the current magnitude of the

monitored circuit. BE1-50 relay functions are illustrated in Figure 3-1 and described in the following

paragraphs.

Figure 3-1. Function Block Diagram

STEP-DOWN TRANSFORMER

Monitored system currents are applied to the primaries of internal current transformers and stepped down

to internal circuit levels. The internal current transformers provide 1,500 V of isolation for the twelve-volt

logic circuits of the relay.

FULL-WAVE RECTIFIERS

Outputs from each step-down transformer are full-wave rectified and applied to resistor networks to

develop voltages that represent the magnitude of the monitored system currents.

RESPONSE CHARACTERISTICS

Input current signals are rectified and passed through a low pass filter. Filtering smoothes out current

spikes and provides a degree of security against operation on short-term transients.
Filtering also smoothes out the harmonic component effects on current signals. Harmonic component

effects are reduced approximately by 1/n where n is the order of the harmonic. For example, the third

harmonic effect is reduced by filtering to 1/3 of what is would be without filtering. With filtering, the

response characteristics are similar to those of electromechanical relays.
9171000990 Rev F

BE1-50 Functional Description

3-1