Output contacts, Temperature, Type tests – Basler Electric BE1-64F User Manual

Page 10

Advertising
background image

Trip Function:

5,000

Ω, ±200 Ω

Pre-Alarm Function:

20,000

Ω, ±1,000 Ω

Figure 1-1. Sensitivity Characteristic

Output Contacts

Type:

Form A, B

Functions:

Ground Trip, Pre-Alarm, Power Fail

Resistive Ratings

120/240 Vac:

Make 30 Aac for 0.2 s, carry 7 Aac continuously, and break 7 Aac

250 Vdc:

Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously, and
break 0.3 Adc

500 Vdc:

Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously, and
break 0.1 Adc

Inductive Ratings

120/240 Vac, 125/250 Vdc:

Make and carry 30 A for 0.2 s, carry 7 A continuously, and
break 0.3 A (L/R = 0.04)

Contact Configurations

Ground Trip:

Form A, close on ground trip condition

Pre-Alarm:

Form A, close on pre-alarm condition

Power Fail:

Form B, close on loss of operating power

Terminal Assignments

Ground Trip:

A6, A7

Pre-Alarm:

A4, A5

Power Fail:

A8, A9

Temperature

Operating:

–40 to 70

°C (–40 to 158°F)

Storage:

–40 to 85

°C (–40 to 185°F)

Type Tests

Vibration:

IEC 255-21-1

Shock:

IEC 255-21-2

Surge Withstand Capability:

IEEE C37.90.1-1989

Radio Interference:

IEC 61000-4-3

Electrostatic Discharge:

IEC 255-22-2

Isolation:

Power, Block inputs withstand 1,500 Vac for one minute. Output contact
sets withstand 2,000 Vac for one minute. Field connection tested to
IEEE 421.3.

0

100

200

300

400

500

600

700

800

900

0

100

200

300

400

500

600

700

R

el

ay

S

en

si

ti

v

it

y

in

k

-ohm

s

DC Fault Voltage

Typical Sensitivity

Alarm

Trip

1-2

BE1-64F General Information

9367200990 Rev B

Advertising