Storage, Pre-alarm jumper – Basler Electric BE1-64F User Manual

Page 22

Advertising
background image

4-4

BE1-64F Installation

9367200990 Rev B

STORAGE

If the BE1-64F relay will not be installed immediately, store it in its original shipping carton in a moisture-
and dust-free environment.

This device contains long-life, aluminum electrolytic capacitors. For devices that are not in service (spares
in storage), the life of these capacitors can be maximized by energizing the BE1-64F for 30 minutes once
per year.

PRE-ALARM JUMPER

The pre-alarm jumper (J1) can be positioned by the user to enable or disable pre-alarm annunciation. J1
is located on the circuit board of the draw-out assembly (Figure 4-5). J1 is accessed by loosening the two
captive front-panel screws and removing the draw-out assembly from the case.

Figure 4-5. Pre-Alarm Jumper Location

Table 4-1 lists the jumper positions required to enable and disable the pre-alarm function.

Table 4-1. Pre-Alarm Jumper Positions

Pre-Alarm Annunciation

Jumper Position (P1 Pins)

Enabled 1

to

2

Disabled 2

to

3

CAUTION

Observe all applicable electrostatic discharge (ESD) precautions when handling
the draw-out assembly.