SECTION 3

FUNCTIONAL DESCRIPTION

INTRODUCTION

The BE1-64F Ground Fault Relay detects and annunciates ground faults in the normally ungrounded field
circuit of a synchronous machine.

The BE1-64F applies a dc voltage between the field circuit and ground. When a ground fault occurs, the
BE1-64F detects the flow of current and annunciates the fault. Detection of ground faults by the BE1-64F
depends upon the nominal field voltage and the location of the ground fault in the field winding.

BE1-64F FUNCTION BLOCKS

BE1-64F functions are illustrated in Figure 3-1. The following paragraphs describe each of the function
blocks illustrated in Figure 3-1.

Figure 3-1. BE1-64F Function Block Diagram

Power Input

Operating power applied to terminals A12 (line) and A11 (neutral) is stepped down and applied to the
power supplies in the relay. The power input accepts voltage in the range of 90 to 132 Vac.

Power Supplies

Stepped-down ac voltage from the power input is rectified, filtered, and regulated. The power supplies
apply regulated dc voltage to internal relay circuitry and supply the dc voltage impressed across the
protected circuit and ground.

POWER INPUT

BLOCK INPUT

LOSS OF AC

POWER

ALARM

OUTPUT

CONTACT

POWER

SUPPLIES

FIELD (F-) AND

ROTOR

GROUND

INTERFACE

CURRENT

DETECTOR AND

REFERENCE

TRIP

COMPARATOR

ALARM

COMPARATOR

GND TRIP

OUTPUT

CONTACT

PRE-ALARM

OUTPUT

CONTACT

TRIP/ TEST

(Not supplied on

P/N 9367200104)

TARGET

RESET

TO INTERNAL

CIRCUITS

A1:

F-

A3:

GND

(CORE)

A10:

LINE

A11:

NEUTRAL

A12:

LINE

A13:

CHASSIS

GND

A6

PRE-

ALARM

A4

A5

A8

A9

GND
TRIP

PWR

FAIL

A7

P0024-16

9367200990 Rev B

BE1-64F Functional Description

3-1

Advertising