Block Input
1. Place switch S2 in the closed position.
2. Place switch S1 in the Pre-Alarm position. The relay should not respond with an output contact
closure or a front panel indication.
3. Place S1 in the Ground Alarm position. The relay should not respond with an output contact closure
or a front panel indication.
4. Open switch S2 and verify that the relay responds to the ground alarm condition.
9367200990 Rev B
BE1-64F Testing