Block input – Basler Electric BE1-64F User Manual

Page 27

Advertising
background image

Block Input

1. Place switch S2 in the closed position.

2. Place switch S1 in the Pre-Alarm position. The relay should not respond with an output contact

closure or a front panel indication.

3. Place S1 in the Ground Alarm position. The relay should not respond with an output contact closure

or a front panel indication.

4. Open switch S2 and verify that the relay responds to the ground alarm condition.

9367200990 Rev B

BE1-64F Testing