Basler Electric BE1-40Q User Manual
Page 16
Locator
Description
F
Output Test Pushbutton. This pushbutton allows manual actuation of the output relay.
Output relay actuation is achieved by inserting a nonconductive rod through the front
panel access hole.
G
Target Indicator. The electronically latched red target indicator illuminates when the
corresponding output relay energizes. To ensure proper operation of the current-operated
target, the current flowing through the trip circuit must be 200 mA or higher. The target
indicator is reset by operating the target reset switch (locator D).
H
Time Delay Selectors. Two thumbwheel switches select the trip time delay. The left
thumbwheel represents seconds; the right thumbwheel represents tenths of a second.
I
Range Switch. Two-position switch selects the reactive power range (HI or LOW) desired.
2-2
BE1-40Q Controls and Indicators