Timing verification, Relay characteristics verification, Preliminary – Basler Electric BE1-40Q User Manual

Page 42: Timing, Verification, Relay, Characteristics

Advertising
background image

Step 9. Repeat Steps 7 and 8 for each TAP setting, verifying both the HI and LOW range setpoints. The

pickup tolerance should be

±2% of the front panel setting or 0.1 var, whichever is greater.

Timing Verification

Step 1. Connect the test circuit as shown in Figure 5-2.

Step 2. Connect a timer to record the time interval from application of the test current that will be

applied in Step 6, to the change of state of the output relay. If a normally open contact has been
selected, a trip will occur when the contact closes; normally closed contacts will open to trip.

Step 3. Make the following front panel adjustments on the BE1-40Q relay:

RANGE switch - LOW position

TAP switch - Position A (minimum)

TIME DELAY switches - 11 (1.1 second)

Step 4. Apply appropriate operating power, depending on the power supply option, to terminals 3 and 4.

The POWER LED should illuminate.

Step 5. Adjust the voltage source to the nominal value of the sensing input as designated by the second

digit of the style number.

Step 6. Adjust the current source to produce a 60

° lagging current that steps from zero magnitude to the

test current value shown in Table 5-2.

Table 5-2. Test Current

Second Digit of

Style Number

Nominal Ac

Voltage

Pickup Current

Test Current

2

120

0.072 A

0.144 A

3

120

0.361 A

0.722 A

5

208

0.083 A

0.166 A

6

208

0.416 A

0.832 A

8

240

0.072 A

0.144 A

9

240

0.361 A

0.722 A

Step 7. The actual time delay should be 1.05 to 1.15 seconds.

Step 8. Adjust the TIME DELAY switches to a setting of 55 (5.5 seconds), and repeat Step 6. The time

delay should be 5.22 to 5.77 seconds.

Step 9. Adjust the TIME DELAY switches to a setting of 99 (9.9 seconds), and repeat Step 6. The time

delay should be 9.40 to 10.39 seconds.

Relay Characteristics Verification

Preliminary

Step 1. Connect the test circuit shown in Figure 5-2.

Step 2. Adjust the BE1-40Q relay for the desired pickup value as specified by the generator application

or the test setup capabilities.

Step 3. Adjust the TIME DELAY switches to a minimum value (e.g., 0.1, 0.2, or 0.3 seconds).

Step 4. Adjust the voltage source to the nominal value of the sensing input as designated by the second

digit of the style number, at a leading phase angle of 150

°.

NOTE

The test current given in Table 5-2 is twice the pickup current.

5-4

BE1-40Q Setting and Testing

9171500990 Rev N

Advertising