= (13.33 Mvar)



12800

3

= 1804 A

Step 3. Specify a BE1-40Q relay having a nominal sensing range of 120 V

LL

(for a PT ratio of

12800/120).

Step 4. Determine the desired secondary current.

Secondary current

=

Ratio

CT

Current

Primary

=

5000/5

1804

= 1.8 A

Step 5. Determine the pickup.

Pickup

=

relay

relay

I

V

×

3

=

8

.

1

3

120 ×

= 125

= Low Range, TAP position E (Table 1-1)

OPERATIONAL TEST

Introduction

The following procedures verify proper relay operation and calibration.

Results obtained from these procedures may no fall within specified tolerances. When evaluating results,
consider three prominent factors:
• Test equipment accuracy
• Testing method
• External test set components tolerance level

Pickup Verification

Step 1. Connect the test circuit as shown in Figure 5-2. Apply appropriate operating power, depending

on the power supply option (refer to the Style Chart in Section 1), to terminals 3 and 4. The
POWER LED should illuminate.

Step 2. For relay styles with target indicators, actuate the target reset switch to insure that the target is

reset.

Step 3. Make the following front panel adjustments on the BE1-40Q relay:

RANGE switch - LOW position

TAP switch - Position A (minimum)

TIME DELAY switches - 10 (1.0 second)

Step 4. If equipped with a power supply status output relay (option 2-S), verify that the contact is open

when external power is applied. Remove input power and verify that the status contacts close.
Re-apply external power.

5-2