BE1-60 General Information

1-5

SPECIFICATIONS

BE1-60 electrical and physical specifications are listed in the following paragraphs. Specifications are
subject to change without notice.

Sensing

Frequency

Nominal:

60

Hz

Range:

45 to 65 Hz

Burden:

1 VA per phase, maximum

Voltage

Nominal

Rating

3-Phase

Wye:

208

V

L-L

3-Phase

Delta:

120

V

L-L

1-Phase:

120

Vac

Range:

60 to 125% of nominal

Maximum Continuous:

160% of nominal

Pickup

Range:

5 to 50% of nominal

Accuracy:

1 V or 5% of setting, whichever is greater

Increment: 5%

Dropout

90% of pickup or greater

Timing

150 milliseconds or less for voltage differences greater than three times the setting

Power Supply

The five power supply types available for the BE1-60 are summarized in Table 1-1.

Table 1-1. Power Supply Types and Specifications

Input Voltage

Type

Nominal

Range

Burden at

Nominal

O (mid range)

48 Vdc

24 to 150 Vdc

1.1 W

P (mid range)

125 Vdc
120 Vac

24 to 150 Vdc
90 to 132 Vac

1.4 W

11.2 VA

R (low range)

24 Vdc

12 to 32 Vdc

1.2 W

S (mid range)

48 Vdc

125 Vdc

24 to 150 Vdc
24 to 150 Vdc

1.1 W
1.4 W

T (high range)

250 Vdc
240 Vac

62 to 280 Vdc
90 to 270 Vac

1.6 W

18.8 VA

∗ The type R power supply initially requires 14 Vdc to begin operating. Once operating, the voltage may
be reduced and operation will continue.

Target Indicators

Targets may be specified as either internally operated or current operated by a minimum of 0.2 amperes
through the output trip circuit. When current operated, the output circuit must be limited to 30 amperes for
0.2 seconds, 7 amperes for 2 minutes, and 3 amperes continuously.