Internally operated targets, Current operated targets – Basler Electric BE1-60 User Manual

Page 19

Advertising
background image

9170700990 Rev D

BE1-60 Functional Description

3-3

Internally Operated Targets

The relay trip outputs are directly applied to drive the appropriate target indicator. Each indicator is
illuminated regardless of the current level in the trip circuit.

Current Operated Targets

A current operated target is triggered by closure of the corresponding output contact and the presence of
at least 200 milliamperes of current flowing in the trip circuit.

NOTE

Prior to September 2007, BE1-60 target indicators consisted of magnetically
latched, disc indicators. These mechanically latched target indicators have been
replaced by the electronically latched LED targets in use today.

Advertising