Outputs, Resistive ratings, Inductive ratings – Basler Electric BE1-60 User Manual

Page 14: Shock, Vibration, Dielectric strength, Surge withstand capability, Radio frequency interference (rfi), Fast transient, Impulse

Advertising
background image

1-6

BE1-60 General Information

9170700990 Rev D

Outputs

Resistive Ratings

120 Vac:

Make, break, and carry 7 Aac continuously

250 Vdc:

Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously,
and break 0.3 Adc

500 Vdc:

Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously, and break 0.3
Adc

Inductive Ratings

120 Vac, 125 Vdc, 250 Vdc:

Break 0.3 A (L/R = 0.04)

Shock

Withstands 15 G in each of three mutually perpendicular planes.

Vibration

Withstands 2 G in each of three mutually perpendicular axes, swept over the range of 10 to 500 Hz for a
total of six sweeps, 15 minutes each sweep.

Dielectric Strength

Complies with IEC 60255-5 and IEEE C37.90 one-minute dielectric (high potential) tests as follows:

All circuits to ground:

2121 Vdc

Input to output circuits:

1500 Vac or 2121 Vdc

Surge Withstand Capability

Qualified to IEEE C37.90 (transient immunity and radiated susceptibility), IEC 60255-5 (impulse
requirements), and IEC60255-5/6 (surge requirements).

Radio Frequency Interference (RFI)

Type tested using a 5 W, hand-held transceiver in the ranges of 144 and 440 MHz with the antenna
placed within 6 inches (152 millimeters) of the relay.

Fast Transient

Qualified to IEEE C37.90.

Impulse

Qualified to IEC 60255-5.

Temperature

Operating: –40

°C to 70°C (–40°F to 158°F)

Storage: –65

°C to 100°C (–85°F to 212°F)

UL Recognition

Recognized per Standard 508, UL file number E97033. Note: Output contacts are not UL-recognized for
voltages greater than 250 V.

GOST-R

Gost-R certified No. POCC US.ME05.B03391; complies with the relevant standards of Gosstandart of
Russia. Issued by accredited certification body POCC RU.0001.11ME05.

Weight

14.25 lb (6.46 kg) maximum

Case Size

S1 (Refer to Section 4, Installation for case dimensions.)

Advertising