BE1-60 General Information

1-1

SECTION 1

GENERAL INFORMATION

INTRODUCTION

The BE1-60 Voltage Balance Relay provides a high-speed response to block other devices from incorrect
operation resulting from a blown fuse or other fault in a potential transformer circuit. The BE1-60 detects
these conditions, initiates corrective action, and indicates the problem and location.

Equipment benefiting from BE1-60 protection includes overcurrent relays (voltage controlled or voltage
restrained types), impedance measuring relays, synchronizing relays, voltage regulators, and static
excitation systems.

APPLICATION

In the typical application shown in Figure 1-1, a generator is equipped with a static exciter and is
protected by voltage controlled or voltage restrained time-overcurrent relays and other devices.

52

POWER

POTENTIAL

TRANSFORMER

SHUTDOWN

CONTACTOR

POWER

INPUT

CKT 1

BE1-60

CKT 2

SENSING

INPUT

STATIC

EXCITER

SENSING

POTENTIAL

TRANSFORMER

GEN

BE1-51/27C

OR

BE1-51/27R

60

FIELD

D2817-15

07-14-98

Figure 1-1. Typical Application of BE1-60 Relay