144

9369700990 Rev R

Verify that the FCR setpoint follows (auto-tracks) the AVR setpoint, then transfer. ............. ________

Use the BESTCOMS Analysis screen to perform a step response in AVR mode. ............... ________

Review the PID numbers. ...................................................................................................... ________

On the Configuration tab of the BESTCOMS Limiter screen, turn all Limiters off. ................ ________

Perform a 2% voltage step response and record performance to verify stability. ................. ________

Adjust the PID parameters of the DECS-400 until desired performance is achieved. If
performance appears stable, repeat with 5% step changes. ................................................ ________

Place the Start/Stop switch in the Stop position. ................................................................... ________

Place the system in AVR mode. ............................................................................................ ________

Monitor the generator voltage soft-start time. ........................................................................ ________

Place the Start/Stop switch in the Start position. ................................................................... ________

Raise the terminal voltage to the setpoint. ............................................................................ ________

TUNING SUGGESTION

Assuming that T’do (main field) and Te (exciter field) is known (as applicable for
main field static exciter or exciter field voltage regulator application), increasing
Kg will speed the response time of the generator. See Figure 104.

Figure 104. Kg Gain Effect on Generator Performance

Commissioning

DECS-400