Holding registers for setpoint parameters – Basler Electric DECS-400 User Manual

Page 230

Advertising
background image

218

9369700990 Rev R

Registers

Data Description

Access

Data

Format

40726

Enables traverse rate to the pre-position 1 for the mode

RW

UINT16

40727

Enables traverse rate to the pre-position 2 for the mode

RW

UINT16

40728

Enables traverse rate to the pre-position 1 for the mode

RW

UINT16

40730 to
40899

Reserved for future C4 use

R

Not

Defined

40900

Traverse time, in seconds, between mode’s min and max settings

RW

FLOAT

40902

Traverse time, in seconds, between mode’s min and max settings

RW

FLOAT

40904

Traverse time, in seconds, between mode’s min and max settings

RW

FLOAT

40906

Traverse time, in seconds, between mode’s min and max settings

RW

FLOAT

40908

Traverse time, in seconds, between mode’s min and max settings

RW

FLOAT

40910

Traverse time, in seconds, between mode’s min and max settings

RW

FLOAT

40912

Traverse time, in seconds, between mode’s min and max settings

RW

FLOAT

40914

Traverse time, in seconds, between mode’s min and max settings

RW

FLOAT

40916

Traverse time, in seconds, between mode’s min and max settings

RW

FLOAT

40918

Traverse time, in seconds, between mode’s min and max settings

RW

FLOAT

Holding Registers for Setpoint Parameters

Table 39. Information Category C5—Setpoint Parameters

Registers

Data Description

Access

Data

Format

40701

FCR pre-position 1 mode: 0=maintained, 1=release

RW

UINT16

40702

AVR pre-position 1 mode: 0=maintained, 1=release

RW

UINT16

40703

VAR pre-position 1 mode: 0=maintained, 1=release

RW

UINT16

40704

PF pre-position 1 mode: 0=maintained, 1=release

RW

UINT16

40705

FCR pre-position 2 mode: 0=maintained, 1=release

RW

UINT16

40706

AVR pre-position 2 mode: 0=maintained, 1=release

RW

UINT16

40707

VAR pre-position 2 mode: 0=maintained, 1=release

RW

UINT16

40708

PF pre-position 2 mode: 0=maintained, 1=release

RW

UINT16

40709

FVR pre-position 1 mode: 0=maintained, 1=release

RW

UINT16

40710

FVR pre-position 2 mode: 0=maintained, 1=release

RW

UINT16

40751

FCR (Field Current Regulator) mode setpoint in amps; adjustment range is
determined by registers (40761-62) and (40769-70)

RW

FLOAT

40753

AVR (Automatic Voltage Regulator) mode setpoint in volts; adjustment
range is determined by registers(40763-64) and (40771-72)

RW

FLOAT

40755

VAR mode setpoint in kvars; adjustment range is determined by registers
(40765-66) and (40773-74)

RW

FLOAT

40757

PF mode setpoint; adjustment range is determined by registers (40767-68)
and (40775-76)

RW

FLOAT

40759

Reactive Droop setting in % of rated generator voltage; adjustable from -30
to +30% in .1% increments

RW

FLOAT

40761

FCR minimum setpoint (in amps) = % of nominal x rated field current:(regs.
40801-02) x (regs. 40479-80) / 100

R

FLOAT

40763

AVR minimum setpoint (in volts) = % of nominal x rated generator
voltage:(regs. 40803-04) x (regs. 40473-74) / 100

R

FLOAT

40765

VAR minimum setpoint (in kvars) = % of nominal x rated generator
VA:(regs. 40805-06) x rated VA / 100

R

FLOAT

40767

PF maximum setpoint = registers 40807-08

R

FLOAT

40769

FCR maximum setpoint (in amps) = % of nominal x rated field current:(regs.
40809-10) x (regs. 40479-80) / 100

R

FLOAT

40771

AVR maximum setpoint (in volts) = % of nominal x rated generator
voltage:(regs. 40811-12) x (regs. 40473-74) / 100

R

FLOAT

40773

VAR maximum setpoint (in kvars) = % of nominal x rated generator
VA:(regs. 40813-14) x rated VA / 100

R

FLOAT

40775

PF minimum setpoint = registers 40815-16

R

FLOAT

40777

FCR mode traverse rate, adjustable from 10 to 200 seconds in 1 second
increments

RW

FLOAT