BECKHOFF CX9020 User Manual

Page 18

Advertising
background image

Mounting and wiring

Correct installation position

The high performance and the compact design of the CX9020 systems may result in increased heat
generation. The heat is dissipated via a passive ventilation system. This system requires the unit to be
mounted correctly. Ventilation openings are located at the top and bottom of the housing. The system
therefore has to be installed horizontally. This ensures optimum air flow.

Incorrect installation positions

The CX9020 system must not be operated vertically on the top­hat rail. A vertical position would lead to
insufficient CPU ventilation, since the ventilation openings are located on the top and bottom of the housing.
Installation of the system on its side would also lead to inadequate ventilation.

invalid installation position 

invalid installation position 

CX9020

18

Version 1.1

Advertising