BECKHOFF CX9020 User Manual

Page 33

Advertising
background image

Commissioning

In the eSUPS_ImmediateShutdown mode a QuickShutdown is executed immediately without saving data.

In the eSUPS_CheckPowerStatus mode only a check is performed as to whether a power failure has
occurred. If this is the case, the module only switches back to the PowerOK state after the expiry of
tRecoverTime (10s).

Independent of the mode and thus independent of the saving or the shutting down of the controller, the UPS
switches the main board off after the capacitors have discharged, even if the voltage has returned in the
meantime.

Attention

Caution when using files:

If other applications or the PLC keep other files open or write to them, this can lead to faulty
files if the UPS switches off the controller.

If the EWF is used, the TwinCAT\Boot folder must be located on an unprotected partition (see in the registry:
HKEY_LOCAL_MACHINE\SOFTWARE\Beckhoff\TwinCAT\System\BootPrjPath).

If the FBWF is used, must the TwinCAT\Boot folder must be excluded from the protection (see Beckhoff
FBWF Manager, Exclusion Settings).

FUNCTION_BLOCK FB_S_UPS_CX9020_U900

VAR_INPUT

VAR_INPUT
    sNetID     : T_AmsNetId := '';     (* '' = local netid *)
    iPLCPort    : UINT := AMSPORT_R0_PLC_RTS1; (* PLC Runtime System for writing persistent data *)
    iUPSPort    : UINT := 16#4A8;         (* Port for reading Power State of UPS, dafault 16#4A8 *)
    tTimeout    : TIME := DEFAULT_ADS_TIMEOUT; (* ADS Timeout *)
    eUpsMode    : E_S_UPS_Mode := eSUPS_WrPersistData_Shutdown; (* UPS mode (w/wo writing persistent
data, w/wo shutdown) *)
    ePersistentMode : E_PersistentMode := SPDM_2PASS; (* mode for writing persistent data *)
    tRecoverTime : TIME := T#10s;         (* ON time to recover from short power failure in mode

CX9020

33

Version 1.1

Advertising