18.0 Set the dosing OnTime and Off Time

A dosing cycle includes the OnTime and the OffTime that the peristaltic pump
doses the system for. The arrow symbol on the display will fl ash during the dose
cycle. Adjustments for OnTime and OffTime will be required so that three dosing
cycles only change the pH value by 0.1 pH.
• ‘OnTime’ is the length of time the peristaltic pump will dose for. The ‘OnTime’

can be set from 1 to 60 seconds.

• ‘OffTime’ is the delay time between each dose. This gives the system time to

mix the pH stock solution thoroughly, so the pH controller connect can measure
the changes being made before needing to dose again. The ‘OffTime’ can be set
from 1 to 60 minutes.

• Start with a long ‘OffTime’ and adjust back as you go. The more thorough the

mixing in the tank, the shorter the ‘OffTime’ can be.

To set the OnTime value:

Press ‘menu’.

Press ‘

’ to fi nd ‘OnTime’. Press ‘enter’.

Press ‘

’ or ‘’ to select the dosing on time in

seconds. Press ‘enter’ to save.

To set the OffTime value:

Press ‘

’ to fi nd ‘OffTime’. Press ‘enter’.

Press ‘

’ or ‘’ to select the dosing off time in

minutes. Press ‘enter’ to save.

1

1

2

2

3