Ventilation and combustion air, Burner installation – Boyertown Regal Oil Furnace Nrg Max User Manual

Page 15

Advertising
background image

15

Vent Dampers

Do not install a thermal type vent damper on the furnace. Failure to comply could result in severe
personal injury, death or substantial property damage. If a vent damper is required, use only a
motorized damper, wired and installed following the vent damper manufacturers instructions.

Ventilation and Combustion Air

Appliances shall be installed in a location where the facilities for ventilation permit the satisfactory
combustion of oil, proper venting and the maintenance of ambient temperature at safe limits under
normal conditions of use. The burner requires a generous amount of clean combustion air to operate
safely. The furnace room must be well ventilated to allow sufficient make-up air to support
combustion.

Inadequate combustion air may result in erratic operation of the burner, noisy combustion or fuel
odors in the air. NEVER BLOCK THE FURNACE FROM THE SUPPLY OF COMBUSTION AIR.
Remember, your need for outside air will be greatly increased if you have a vented dryer in the
basement or other venting fans in the home. Do not install an exhaust fan in the same room as the
furnace.

In unconfined spaces in buildings of conventional construction, infiltration is adequate to provide air
for ventilation and combustion. If the unconfined space is within a building having insufficient air
because of tight construction, the air required for combustion and ventilation shall be obtained from
outdoors or from spaces freely communicating with the outdoors. In this situation, permanent
openings having a total free opening area of not less than 1 square inch per 5000Btu/Hr of total input
of all appliances must be provided.

If the furnace is located in a confined space (A space whose volume is less than 50 cubic feet per
1000Btu/Hr of the combined input ratings of all appliances installed in that space) the confined space
shall have two permanent openings, one 6 inches from the top of the space and one 6 inches from the
bottom of the space. Each opening shall have a free area opening of not less than 1 square inch per
1000Btu/Hr of total input rating of all appliances in the enclosure freely communicating with interior
areas having adequate infiltration with the outside.

If adequate infiltration air is not available the confined space shall be fitted with two openings, one 6
inches from the top of the enclosure and one 6 inches from the bottom of the enclosure. Each opening
shall have a free area of at least 1 square inch per 2000Btu/Hr of the total input of the appliances in
the enclosure.

In calculating free area, consideration must be given to the blocking effect of louvers, screens or grills
protesting the opening. Screens used shall not be less than ¼” mesh and shall be readily accessible for
cleaning.

Burner Installation

Remove the oil burner from its shipping carton and inspect thoroughly. Verify that the
correct burner combination and nozzle is installed in the burner as shipped.

Read the oil burner manual included in the shipping carton and follow the instructions for preparing
and installing the burner. Refer to Table 9, Table 10, or Table 11 for the burner specifications for
your unit.

A jumper wire must be placed on the “T-T” connection on the oil burner primary safety control.

On units which can be multi fired, a nozzle change may be required. Follow the oil burner manuals
instructions for the proper installation of the nozzle.

NOTICE

Advertising