Boyertown Regal Oil Furnace Nrg Max User Manual

Page 25

Advertising
background image

25

7. Vacuum Gauge 0-30 in. of Hg
8. Volt meter
9. Amp meter

Burner Adjustments

Allow the burner to operate for at least 10 minutes before making the following adjustments. The
factory burner settings may not be suitable for specific job conditions.
Do not attempt to make any adjustments or start the furnace without the proper equipment.

1. A 5/16” diameter hole will be required in the flue pipe between the furnace and the barometric

damper as close to the furnace as possible.

2. Set the draft regulator (barometric damper) using a draft gauge to obtain a negative draft over-fire

of -.01 to -.02 in. W.C.

3. Pump pressure – Install a pump pressure gauge in the oil pump following the oil burner

manufacturers’ recommendations. Adjust to obtain required pressure as necessary.

4. Combustion Set-up – The air settings shown in Table 8 thru Table 10 are approximate. The

burner must be adjusted during actual field installed conditions. Failure to do so will result in
poor performance and nuisance service calls. After proper draft and oil pressure have been
established:

a. Begin to close the air band to create a slight trace of smoke as noted on the Bacharach or

equivalent smoke tester scale.

b. Take a flue gas sample and note the CO

2

reading. It will be about 12% to 14%

c. Open the air band to reduce the CO

2

approximately 1%. The desired CO

2

setting for all

units should be 11% to 13%

d. Check for “0” smoke. Head settings and/or air band may be altered to obtain the above

results. Lock the air band and head setting screws in place.

The above procedure will give a built in margin to ensure clean operation throughout the heating
season. Should draft conditions vary, lint accumulate in the fan, heavier oil delivered, or other
adverse conditions be encountered you will have a reasonable margin of built in protection before
smoke generation begins.

5. Flue Gas Temperature - The flue gas temperature will vary to some degree depending on BTU

inputs, duct design and the air flow across the heat exchanger. The suggested minimum NET
stack temperature is 350

º

F, and the maximum stack temperature is 550

º

F. The lower the stack

temperature, the higher the efficiency; however, stack temperatures under 350

º

F may cause

condensation which in turn may cause metal corrosion.

6. Temperature Rise - Supply air temperature minus return air temperature. The temperature rise

across the furnace (operating at steady state conditions) should be approximately 75

º

F. A higher

temperature rise would slightly lower the efficiency. The supply air temperature should be
measured in the supply air trunk-line approximately 12 inches down stream of the plenum.
Do not exceed the maximum temperature rise as listed on the furnace nameplate.

7. Check operation of the cad cell relay by removing cad cell wire from external terminal of primary

safety control to ensure that it goes off on safety.

8. Check blower motor amperage under both heating and air conditioning loads and ensure that the

amperage is less than the full load nameplate amperage of the blower motor.

Advertising