Maintenance, General, Cori-flow sensor – Bronkhorst CORI-FLOW User Manual

Page 22: Controllers, Control valves, Solenoid valves, Vary-p valve, 4 maintenance, 1 general, 2 cori-flow sensor

Advertising
background image

BRONKHORST CORI-TECH B.V.

4 MAINTENANCE

4.1 General

No routine maintenance is required to be performed on the meters or controllers. In case of severe

contamination it may be required to clean the valve orifice separately.

4.2 CORI-FLOW sensor

The CORI-FLOW sensor is constructed in such a way that there is little dead volume.

The sensor is maintenance free.

4.3 Controllers

All sensor types can be combined with a control valve to be operated together as a control loop. Controller

systems are either available as separate units; a sensor and a control valve, or as an integrated unit.

If applicable maintenance procedures are described under “control valves”

4.4 Control valves

Control valves cannot be used for shut-off and/or on-off applications. Pressure surges, as may occur during

system pressurisation or deflation must be avoided.

4.4.1 Solenoid valves

These are considered to be the directly operated control and pilot valves. They can be disassembled in the

field by the user for cleaning and servicing. The parts can be cleaned with a cleaning liquid, or in an

ultrasonic bath.

To disassemble the valve proceed as follows:

a)

disconnect the instrument connector (not necessary with separate valve)

b)

remove the hex nut on top of the valve assembly

c)

lift the cover (coil) assembly

d)

unscrew the flange

e)

lift valve assembly carefully from the base

f)

unscrew set screw for the orifice and subsequently loosen the orifice and the orifice holder

g)

remove the plunger assembly

Clean parts and carefully re-assemble in reverse order. It is recommended to replace the O-rings prior to re-

assembly.

After having re-assembled the control valve, it is recommended to check the control characteristics of the

valve. This can best be done by using a separate variable 15 Vdc power supply source.

Proceed as follows:

-

disconnect the valve leads and connect to supply source

-

apply gas pressure as per working conditions

-

apply power by gradually increasing voltage

-

the valve should open at 7 Vdc ± 3 Vdc

-

the fully opened position is reached at approx. 9 Vdc ± 1.5 Vdc.

In case the valve does not operate within the voltage levels stated, then it must be disassembled, and the

orifice must be adjusted to the proper position.

Re-assemble valve and repeat procedure if required.

4.4.2 Vary-P valve

The vary-P valve is designed to cope with extremely varying process conditions on either upstream or

downstream side of the valve or a combination of these. ∆p can vary over a wide range. The basic control

valve is a direct operated solenoid control valve.

The design has been patented.

For orifice selection and maintenance other than the pilot valve consult the factory.

page 22

9.17.031

Advertising