Table 10.12 symptom chart – Flowserve 3400IQ Digital Positioner User Manual

Page 113

Advertising
background image

3

Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07

flowserve.com

Table 10.12 Symptom Chart

Failure or Problem

Probable Cause(s)

Refer to Section(s)

Valve moves in wrong direction with no

change in input signal

1. May be tubed for wrong air action.

2. Spool stuck.

1. See Air Action in Section 6.

2. See Spool Valve instructions in Logix

3400IQ Digital Positioner IOM.

Unit does not respond to fieldbus

command.

1. Unit is not configured correctly.

1. See Theory of Operation on page 3.

2. Error occurred during calibration.

2. See Calibration in Section 9.

Calibration
LEDs blink YRYR or YRRY after a

Re-Cal operation. Valve stays in fully

open or closed position.

1. Configured for linear on a rotary

mounting.

1. See Re-Cal button Section 9.

2. Feedback linkage out of range.

LEDs blink YRRR after a Re-Cal, or

calibration operation.

1. Valve didn’t fully stroke during

calibration (low or no air supply).

1. See Re-Cal button Section 9.

2. Stuck Spool.

2. See Spool Valve instruction in Logix

3400IQ Digital Positioner IOM.

On a rotary, valve has a dead band at

the fully open or closed position.

1. Mechanical travel is not centered

within the electrical measurement range

(position sensor out of range).

1. See Linear vs. Rotary in Section 6.

Control and Tuning
Valve won’t saturate at closed position.

1. May need to enable MPC

1. See MPC in Section 8.

2. Calibration required.

Valve won’t go below or above a certain

limit.

1. Soft limits are not enabled

1. See Advanced Features in Section 10.

2. MPC is not enabled

Sticking or hunting operation of the

positioner.

1. Contamination of spool valve

assembly

1. See Air Supply Requirements on page

15. See Spool Valve in Section 10.

2. P+I setting incorrect

2. See Setting P+I Parameters in Section 10.

3. Excessive Stiction

3. Enable Hi Friction Feature

Large initial deviation; only present on

initial power-up.

1. Inner loop offset not correct.

1. See Setting P+I Parameters in Section

10.

Stem position movement is not linear

with command.

1. Custom characterization is enabled

1. See Custom Characterization in

Section 10.

Fieldbus Communication
Logix 3400IQ digital positioner will not

communicate with fieldbus.

1. Power problem.

1. See Wiring the Logix 3400IQ Digital

Positioner to a Fieldbus Network on

page 19.

2. FB card connection.

2. Verify FB protocol being used.

Configurator displays ‘Unknown’ after

it connects.

1. DD has not been loaded in the

configurator correctly.

1. Reload DD making sure Valtek

products are listed.

Erratic communications occur.

1. Maximum cable length or impedance

exceeded

1. See Wiring the Logix 3400IQ Digital

Positioner to a Fieldbus Network on

page 19.

2. Card not receiving enough power.

(Laptop batteries possibly low)

2. Refer to AGA-181 for Network

checkout procedure.

3. Interference with I.S. barrier

Alarms
Temperature alarm occurs.

1. Ambient temperature has exceeded

electronics ratings

1. See Temperature Alarm in Section 8.

Hall sensor alarm occurs.

1. Hall connector may have bad

connection

1. See Hall sensor Alarm in Section 8.

2. Sensor may be damaged
3. Low air supply pressure

3. Check air supply

Modulator current alarm occurs.

1. Modulator minimum pressure may

be too low.

1. See Modulator current Alarm in

Section 8.

2. Clogged orifice
3. Bad cable connection

EEPROM checksum alarm occurs.

1. Error when reading non-volatile

memory storage

1. See EEPROM checksum Alarm in

Section 8.

Multiple internal flags occur.

1. Bad micro-controller on main PCB

assembly.